OSP-P20L
OSP-P20L Alarm & Error List
ALARM & ERROR LIST
9800 Numeric values only, decimal point not allowed
A character specified as an input value is not a numeric value (including decimal point).
[Remedy]
Input numeric characters.
9801 Trigger address not set
The trigger address was not set before setting the trigger address condition.
[Remedy]
Set the trigger address before setting the trigger address condition.
9802 No reference value for trigger condition, cannot set
The reference value cannot be set because the reference value setting condition is not satisfied.
The reference value can be set only when the trigger signal is not a bit identifier and the trigger condition is set to “= EQU”.
[Remedy]
Change the trigger signal to word or long word.
Set the trigger condition to ”= EQU” before setting the reference value.
9803 Identifier range over
The specified identifier address is outside the processing range.
The address range may be exceeded or the auxiliary information may be abnormal.
[Remedy]
Create and install a correct auxiliary information file.
Specify an identifier address within the processing range.
9804 Input data overflow
The input data is too large or too small.
[Remedy]
Input a correct value.